Connecting to MicroLogix
To connect Ignition to an Allen-Bradley MicroLogix device
-
Go to the Configure section of the Gateway webpage.
-
Scroll down and select OPC-UA > Devices.
-
On the Devices page, find the orange arrow and click on Create new Device.
-
On the Add Device Step 1: Choose Type page, select Allen-Bradley MicroLogix, and click Next.
-
On the New Device page, leave all the default values and type in the following fields:
Name: MicroLogix
Hostname: type the IP address for the PLC, for example 10.20.7.77
-
Click Create New Device.
The Devices page is displayed showing the MicroLogix device is added to Ignition. The Status will show as Disconnected and then Connected.
-
To see all the tags, go to OPC Connections > Quick Client in the Configure section, on the OPC Quick Client page expand the MicroLogix folder which contains all the folders with the individual tags.
Supported MicroLogix Connection Methods
-
MicroLogix 1100 and 1400 direct
-
MicroLogix 1100 and 1400 connected through 1761-NET-ENI
-
MicroLogix 1100/1400 connected through Spectrum Controls WebPort 500
Important
MicroLogix 1200 and 1500 are not fully supported. Browsing is not available on these devices, so the 'Disable Processor Browse' advanced property will need to be set to True on the device connection.
Some Micrologix devices may get stuck in a 'Browse Pending' status. In this case setting the connection path property to 1,0 should resolve the issue.